STRUCTURAL CONCRETE BUILDING CODE (ACI 318M-11) AND COMMENTARY
CODE
COMMENTARY
67
COMMENTARY
5
Fig. R5.3—Flow chart for selection and documentation of concrete proportions.
American Concrete Institute Copyrighted Material—www.concrete.org
68
STRUCTURAL CONCRETE BUILDING CODE (ACI 318M-11) AND COMMENTARY
CODE
COMMENTARY
5.3.1 — Sample standard deviation
5.3.1.1 — Where a concrete production facility has
strength test records not more than 24 months old, a
sample standard deviation, ss , shall be established.
Test records from which ss is calculated:
5
R5.3.1 — Sample standard deviation
The standard deviation established from test records is a
measure of the concrete supplier’s ability to manage variability
of materials, production, and testing of concrete. A test
record obtained less than 24 months before a submittal is
acceptable.
(a) Shall represent materials, quality control procedures, and conditions similar to those expected and
changes in materials and proportions within the test
records shall not have been more restricted than those
for proposed Work;
When a concrete production facility has a suitable record of
30 consecutive tests of similar materials and conditions
expected, the sample standard deviation, ss, is calculated from
those results in accordance with the following formula:
(b) Shall represent concrete produced to meet a
specified compressive strength or strengths within 7 MPa
of fc′ ;
(c) Shall consist of at least 30 consecutive tests or two
groups of consecutive tests totaling at least 30 tests as
defined in 5.6.2.4, except as provided in 5.3.1.2.
5.3.1.2 — Where a concrete production facility does
not have strength test records meeting requirements
of 5.3.1.1(c), but does have test records not more than
24 months old based on 15 to 29 consecutive tests, a
sample standard deviation ss shall be established as
the product of the calculated sample standard deviation
and modification factor of Table 5.3.1.2. To be
acceptable, test records shall meet requirements (a)
and (b) of 5.3.1.1, and represent only a single record
of consecutive tests that span a period of not less than
45 calendar days.
TABLE 5.3.1.2 —MODIFICATION FACTOR FOR
SAMPLE STANDARD DEVIATION WHEN LESS
THAN 30 TESTS ARE AVAILABLE
No. of tests*
Less than 15
Use Table 5.3.2.2
15
1.16
20
1.08
25
1.03
30 or more
*Interpolate
†
Modification factor for sample
standard deviation†
1.00
for intermediate numbers of tests.
Modified sample standard deviation, ss , to be used to determined required
′
average strength, fcr , from 5.3.2.1
2 1/2
Σ ( xi – x )
ss = -----------------------(n – 1)
where
ss =
xi =
x =
n =
sample standard deviation, MPa
individual strength tests as defined in 5.6.2.4
average of n strength test results
number of consecutive strength tests
The sample standard deviation is used to determine the
average strength required in 5.3.2.1.
If two test records are used to obtain at least 30 tests, the
sample standard deviation used shall be the statistical
average of the values calculated from each test record in
accordance with the following formula:
2
2 1/2
( n 1 – 1 ) ( s s1 ) + ( n 2 – 1 ) ( s s2 )
ss = --------------------------------------------------------------------------( n1 + n2 – 2 )
where
= statistical average standard deviation where two
ss
test records are used to estimate the sample standard
deviation
ss1, ss2= sample standard deviations calculated from two
test records, 1 and 2, respectively
n1, n2 = number of tests in each test record, respectively
If less than 30 tests, but at least 15 tests are available, the
calculated sample standard deviation is increased by the
factor given in Table 5.3.1.2. This procedure results in a
more conservative (increased) required average strength.
The factors in Table 5.3.1.2 are based on the sampling
distribution of the sample standard deviation and provide
protection (equivalent to that from a record of 30 tests)
against the possibility that the smaller sample underestimates
the true or universe population standard deviation.
The sample standard deviation used in the calculation of
required average strength should be developed under
American Concrete Institute Copyrighted Material—www.concrete.org
STRUCTURAL CONCRETE BUILDING CODE (ACI 318M-11) AND COMMENTARY
CODE
69
COMMENTARY
conditions “similar to those expected” [see 5.3.1.1(a)]. This
requirement is important to ensure acceptable concrete.
Concrete for background tests to determine sample standard
deviation is considered to be “similar” to that required if
made with the same general types of ingredients under no
more restrictive conditions of control over material quality
and production methods than on the proposed Work, and if
its specified strength does not deviate more than 7 MPa
from the fc′ required [see 5.3.1.1(b)]. A change in the type
of concrete or a major increase in the strength level may
increase the sample standard deviation. Such a situation
might occur with a change in type of aggregate (i.e., from
natural aggregate to lightweight aggregate or vice versa) or
a change from non-air-entrained concrete to air-entrained
concrete. Also, there may be an increase in sample standard
deviation when the average strength level is raised by a
significant amount, although the increment of increase in
sample standard deviation should be somewhat less than
directly proportional to the strength increase. When there is
reasonable doubt, any estimated sample standard deviation
used to calculate the required average strength should
always be on the conservative (high) side.
Note that the Code uses the sample standard deviation in
megapascals instead of the coefficient of variation in
percent. The latter is equal to the former expressed as a
percent of the average strength.
Even when the average strength and sample standard deviation
are of the levels assumed, there will be occasional tests that
fail to meet the acceptance criteria prescribed in 5.6.3.3
(perhaps one test in 100).
5.3.2 — Required average strength
R5.3.2 — Required average strength
5.3.2.1 — Required average compressive strength
′
fcr used as the basis for selection of concrete
proportions shall be determined from Table 5.3.2.1
using the sample standard deviation, ss , calculated in
accordance with 5.3.1.1 or 5.3.1.2.
R5.3.2.1 — Once the sample standard deviation has been
determined, the required average compressive strength, fcr ,
′
is obtained from the larger value computed from Eq. (5-1)
and (5-2) for fc′ of 35 MPa or less, or the larger value
computed from Eq. (5-1) and (5-3) for fc′ over 35 MPa.
Equation (5-1) is based on a probability of 1-in-100 that the
average of three consecutive tests may be below the specified
compressive strength fc′ . Equation (5-2) is based on a
similar probability that an individual test may be more than
35 MPa below the specified compressive strength fc′ .
Equation (5-3) is based on the same 1-in-100 probability
that an individual test may be less than 0.90fc . These equations
′
assume that the sample standard deviation used is equal to
the population value appropriate for an infinite or very large
number of tests. For this reason, use of sample standard
deviations estimated from records of 100 or more tests is
desirable. When 30 tests are available, the probability of
failure will likely be somewhat greater than 1-in-100. The
additional refinements required to achieve the 1-in-100
probability are not considered necessary because of the
TABLE 5.3.2.1 — REQUIRED AVERAGE
COMPRESSIVE STRENGTH WHEN DATA ARE
AVAILABLE TO ESTABLISH A SAMPLE
STANDARD DEVIATION
Specified compressive
strength, MPa
fc′ ≤ 35
fc′ > 35
Required average compressive
strength, MPa
Use the larger value computed
from Eq. (5-1) and (5-2)
′
(5-1)
fcr = fc′ + 1.34ss
fcr = fc′ + 2.33ss – 3.5
′
(5-2)
Use the larger value computed
from Eq. (5-1) and (5-3)
′
(5-1)
fcr = fc′ + 1.34ss
′
(5-3)
fcr = 0.90fc′ + 2.33ss
American Concrete Institute Copyrighted Material—www.concrete.org
5
70
STRUCTURAL CONCRETE BUILDING CODE (ACI 318M-11) AND COMMENTARY
CODE
COMMENTARY
uncertainty inherent in assuming that conditions operating
when the test record was accumulated will be similar to
conditions when the concrete will be produced.
5
5.3.2.2 — When a concrete production facility does
not have field strength test records for calculation of ss
meeting requirements of 5.3.1.1 or 5.3.1.2, fcr shall
′
be determined from Table 5.3.2.2 and documentation
of average strength shall be in accordance with
requirements of 5.3.3.
TABLE 5.3.2.2 — REQUIRED AVERAGE
COMPRESSIVE STRENGTH WHEN DATA ARE
NOT AVAILABLE TO ESTABLISH A SAMPLE
STANDARD DEVIATION
Specified compressive
strength, MPa
Required average compressive
strength, MPa
fc′ < 21
fcr = fc′ + 7.0
′
21 ≤ fc′ ≤ 35
fcr = fc′ + 8.3
′
fc′ > 35
fcr = 1.10fc′ + 5.0
′
5.3.3 — Documentation of average compressive
strength
R5.3.3 — Documentation of average compressive
strength
Documentation that proposed concrete proportions
will produce an average compressive strength equal to
or greater than required average compressive strength
′
fcr (see 5.3.2) shall consist of one or more field
strength test record(s) or trial mixtures. The field
strength test records or trial mixtures shall not be more
than 24 months old and shall conform to 5.3.3.1 and
5.3.3.2, respectively.
Once the required average compressive strength fcr is known,
′
the next step is to select mixture proportions that will produce
an average strength at least as great as the required average
strength, and also meet requirements for applicable exposure
categories of Chapter 4. The documentation may consist of
one or more field strength test record(s) in accordance with
5.3.3.1, or suitable laboratory or field trial mixtures in accordance with 5.3.3.2. Generally, if a test record is used, it will be
the same one that was used for computation of the standard
deviation. However, if this test record shows either lower or
higher average compressive strength than the required average
compressive strength, different proportions may be necessary
or desirable. In such instances, the average from a record of as
few as 10 tests may be used, or the proportions may be established by interpolation between the strengths and proportions
of two such records of consecutive tests. All field test records
for establishing proportions necessary to produce the average
compressive strength are to meet the requirements of 5.3.3.1
for “similar materials and conditions.”
5.3.3.1 — When test records in accordance with
5.3.1.1 or 5.3.1.2 are used to demonstrate that
′
proposed concrete proportions will produce fcr (see
5.3.2), such records shall represent materials and
conditions similar to those expected. Changes in
materials, conditions, and proportions within the test
records shall not have been more restricted than those
for proposed Work. For the purpose of documenting
average strength potential, test records consisting of
less than 30 but not less than 10 consecutive tests are
acceptable provided test records encompass a period
of time not less than 45 days. Required concrete
proportions shall be permitted to be established by
interpolation between the strengths and proportions of
two or more test records, each of which meets other
requirements of this section.
5.3.3.2 — When an acceptable record of field test
results to document the required average strength is not
available, concrete proportions established from trial
mixtures meeting the following requirements shall be
permitted:
For strengths over 35 MPa where the average compressive
strength documentation is based on laboratory trial
mixtures, it may be appropriate to increase fcr calculated in
′
Table 5.3.2.2 to allow for a reduction in strength from
laboratory trials to actual concrete production.
R5.3.3.2 — This section of the Code was modified in ACI
318-08 to clarify the requirements for making trial batches.
(b) For concrete made with more than one type of
cementitious material, the concrete supplier must estab-
American Concrete Institute Copyrighted Material—www.concrete.org
STRUCTURAL CONCRETE BUILDING CODE (ACI 318M-11) AND COMMENTARY
CODE
(a) Materials shall be those for proposed Work;
(b) Trial mixtures with a range of proportions that will
produce a range of compressive strengths encom′
passing fcr and meet the durability requirements of
Chapter 4;
(c) Trial mixtures shall have slumps within the range
specified for the proposed Work; for air-entrained
concrete, air content shall be within the tolerance
specified for the proposed Work;
(d) For each trial mixture, at least two 150 by 300 mm or
three 100 by 200 mm cylinders shall be made and cured
in accordance with ASTM C192M. Cylinders shall be
tested at 28 days or at test age designated for fc′ ;
(e) The compressive strength results, at designated
test age, from the trial mixtures shall be used to
establish the composition of the concrete mixture
proposed for the Work. The proposed concrete
mixture shall achieve an average compressive
strength as required in 5.3.2 and satisfy the applicable durability criteria of Chapter 4.
71
COMMENTARY
lish not only the water-cementitious material ratio but
also the relative proportions of cementitious materials and
admixtures, if any, that will produce the required average
compressive strength and satisfy the durability requirements
of Chapter 4. This will require multiple trial batches with
different mixture proportions. The exact number of
batches will depend on the number of cementitious
materials and the range of their relative proportions.
(d) Starting with the 2008 Code, 5.6.2.4 permits two
cylinder sizes for preparing test specimens for field
acceptance testing.
(e) The compressive strength test results may be analyzed
graphically or using regression models to determine the
water-cementitious material ratio and the relative
proportions of cementitious materials, if other materials
in addition to portland cement are used, that will produce
concrete satisfying the required average compressive
strength fcr .
′
5.4 — Proportioning without field
experience or trial mixtures
R5.4 — Proportioning without field
experience or trial mixtures
5.4.1 — If data required by 5.3 are not available, concrete
proportions shall be based upon other experience or
information, if approved by the licensed design profes′
sional. The required average compressive strength fcr
of concrete produced with materials similar to those
proposed for use shall be at least 8.3 MPa greater
than fc′ . This alternative shall not be used if fc′ is
greater than 35 MPa.
R5.4.1 — When no prior experience (5.3.3.1) or trial
mixture data (5.3.3.2) meeting the requirements of these
sections is available, other experience may be used only
when permission is given. Because combinations of
different ingredients may vary considerably in strength
level, this procedure is not permitted for fc′ greater than
35 MPa and the required average compressive strength
should exceed fc′ by 8.3 MPa. The purpose of this provision
is to allow work to continue when there is an unexpected
interruption in concrete supply and there is not sufficient
time for tests and evaluation or in small structures where the
cost of trial mixture data is not justified.
5.4.2 — Concrete proportioned by this section shall
conform to the durability requirements of Chapter 4
and to compressive strength test criteria of 5.6.
5.5 — Average compressive strength
reduction
As data become available during construction, it shall
be permitted to reduce the amount by which the
′
required average concrete strength, fcr , must exceed
fc′ , provided:
(a) Thirty or more test results are available and
average of test results exceeds that required by
5.3.2.1, using a sample standard deviation calculated
in accordance with 5.3.1.1; or
American Concrete Institute Copyrighted Material—www.concrete.org
5
72
STRUCTURAL CONCRETE BUILDING CODE (ACI 318M-11) AND COMMENTARY
CODE
COMMENTARY
(b) Fifteen to 29 test results are available and
average of test results exceeds that required by
5.3.2.1 using a sample standard deviation calculated
in accordance with 5.3.1.2; and
(c) Requirements
Chapter 4 are met.
for
exposure
categories
of
5
5.6 — Evaluation and acceptance of
concrete
R5.6 — Evaluation and acceptance of
concrete
Once the mixture proportions have been selected and the job
started, the criteria for evaluation and acceptance of the
concrete can be obtained from 5.6.
An effort has been made in the Code to provide a clear-cut
basis for judging the acceptability of the concrete, as well as
to indicate a course of action to be followed when the results
of strength tests are not satisfactory.
5.6.1 — Concrete shall be tested in accordance with
the requirements of 5.6.2 through 5.6.5. The testing
agency performing acceptance testing shall comply
with ASTM C1077. Qualified field testing technicians
shall perform tests on fresh concrete at the job site,
prepare specimens required for curing under field
conditions, prepare specimens required for testing in
the laboratory, and record the temperature of the fresh
concrete when preparing specimens for strength tests.
Qualified laboratory technicians shall perform all
required laboratory tests. All reports of acceptance
tests shall be provided to the licensed design
professional, contractor, concrete producer, and,
when requested, to the owner and the building official.
R5.6.1 — ASTM C10775.3 identifies and defines the duties
and minimum technical requirements and qualifications of
testing laboratory personnel and requirements for testing
concrete and concrete aggregates used in construction.
Inspection and accreditation of testing laboratories is a
process that ensures that they conform to ASTM C1077.
Laboratory and field technicians can establish qualifications
by becoming certified through certification programs. Field
technicians in charge of sampling concrete; testing for
slump, density, yield, air content, and temperature; and
making and curing test specimens should be certified in
accordance with the requirements of ACI Concrete Field
Testing Technician—Grade 1 Certification Program, or an
equivalent program. Concrete testing laboratory personnel
should be certified in accordance with the requirements of
ACI Concrete Laboratory Testing Technician, or Concrete
Strength Testing Technician.
The Code requires testing reports to be distributed to the
parties responsible for the design, construction, and
approval of the work. Such distribution of test reports
should be indicated in contracts for inspection and testing
services. Prompt distribution of testing reports allows for
timely identification of either compliance or the need for
corrective action. A complete record of testing allows the
concrete producer to reliably establish the required average
′
strength fcr for future work.
5.6.2 — Frequency of testing
R5.6.2 — Frequency of testing
5.6.2.1 — Samples for strength tests of each class
of concrete placed each day shall be taken not less
than once a day, nor less than once for each 110 m3 of
concrete, nor less than once for each 460 m2 of
surface area for slabs or walls.
R5.6.2.1 — The following three criteria establish the required
minimum sampling frequency for each class of concrete:
(a) Once each day a given class is placed, nor less than
(b) Once for each 110 m3 of each class placed each day,
nor less than
American Concrete Institute Copyrighted Material—www.concrete.org