Bạn đang xem bản rút gọn của tài liệu. Xem và tải ngay bản đầy đủ của tài liệu tại đây (12.31 MB, 509 trang )
86
STRUCTURAL CONCRETE BUILDING CODE (ACI 318M-11) AND COMMENTARY
CODE
COMMENTARY
6.3.5.3 — They shall not impair significantly the
strength of the construction.
6.3.6 — Conduits, pipes, and sleeves shall be
permitted to be considered as replacing structurally in
compression the displaced concrete provided in
6.3.6.1 through 6.3.6.3.
6
6.3.6.1 — They are not exposed to rusting or other
deterioration.
6.3.6.2 — They are of uncoated or galvanized iron
or steel not thinner than standard Schedule 40 steel
pipe.
6.3.6.3 — They have a nominal inside diameter not
over 50 mm and are spaced not less than three diameters on centers.
6.3.7 — Pipes and fittings shall be designed to resist
effects of the material, pressure, and temperature to
which they will be subjected.
R6.3.7 — The 1983 Code limited the maximum pressure in
embedded pipe to 1.4 MPa, which was considered too
restrictive. Nevertheless, the effects of such pressures and
the expansion of embedded pipe should be considered in the
design of the concrete member.
6.3.8 — No liquid, gas, or vapor, except water not
exceeding 32°C nor 0.35 MPa pressure, shall be
placed in the pipes until the concrete has attained its
design strength.
6.3.9 — In solid slabs, piping, unless it is for radiant
heating or snow melting, shall be placed between top
and bottom reinforcement.
6.3.10 — Specified concrete cover for pipes, conduits,
and fittings shall not be less than 40 mm for concrete
exposed to earth or weather, nor less than 20 mm for
concrete not exposed to weather or in contact with
ground.
6.3.11 — Reinforcement with an area not less than
0.002 times area of concrete section shall be provided
normal to piping.
6.3.12 — Piping and conduit shall be so fabricated and
installed that cutting, bending, or displacement of reinforcement from its proper location will not be required.
6.4 — Construction joints
R6.4 — Construction joints
6.4.1 — Surface of concrete construction joints shall
be cleaned and laitance removed.
For the integrity of the structure, it is important that all
construction joints be defined in construction documents
and constructed as required. Any deviations should be
approved by the licensed design professional.
American Concrete Institute Copyrighted Material—www.concrete.org
STRUCTURAL CONCRETE BUILDING CODE (ACI 318M-11) AND COMMENTARY
87
CODE
COMMENTARY
6.4.2 — Immediately before new concrete is placed,
all construction joints shall be wetted and standing
water removed.
R6.4.2 — The requirements of the 1977 Code for the use of
neat cement on vertical joints have been removed, since it is
rarely practical and can be detrimental where deep forms
and steel congestion prevent proper access. Often wet
blasting and other procedures are more appropriate.
Because the Code sets only minimum standards, the
licensed design professional may have to specify additional
procedures if conditions warrant. The degree to which
mortar batches are needed at the start of concrete placement
depend on concrete proportions, congestion of steel,
vibrator access, and other factors.
6.4.3 — Construction joints shall be so made and
located as not to impair the strength of the structure.
Provision shall be made for transfer of shear and other
forces through construction joints. See 11.6.9.
R6.4.3 — Construction joints should be located where they
will cause the least weakness in the structure. When shear
due to gravity load is not significant, as is usually the case in
the middle of the span of flexural members, a simple
vertical joint may be adequate. Lateral force design may
require special design treatment of construction joints.
Shear keys, intermittent shear keys, diagonal dowels, or the
shear transfer method of 11.6 may be used whenever a force
transfer is required.
6.4.4 — Construction joints in floors shall be located
within the middle third of spans of slabs, beams, and
girders.
6.4.5 — Construction joints in girders shall be offset a
minimum distance of two times the width of intersecting
beams.
6.4.6 — Beams, girders, or slabs supported by
columns or walls shall not be cast or erected until
concrete in the vertical support members is no longer
plastic.
R6.4.6 — Delay in placing concrete in members supported
by columns and walls is necessary to prevent cracking at the
interface of the slab and supporting member caused by
bleeding and settlement of plastic concrete in the supporting
member.
6.4.7 — Beams, girders, haunches, drop panels, shear
caps, and capitals shall be placed monolithically as
part of a slab system, unless otherwise shown in
contract documents.
R6.4.7 — Separate placement of slabs and beams,
haunches, and similar elements is permitted when shown on
the contract documents and where provision has been made
to transfer forces as required in 6.4.3.
American Concrete Institute Copyrighted Material—www.concrete.org
6
88
STRUCTURAL CONCRETE BUILDING CODE (ACI 318M-11) AND COMMENTARY
CODE
Notes
COMMENTARY
6
American Concrete Institute Copyrighted Material—www.concrete.org
STRUCTURAL CONCRETE BUILDING CODE (ACI 318M-11) AND COMMENTARY
89
CHAPTER 7 — DETAILS OF REINFORCEMENT
CODE
COMMENTARY
7.1 — Standard hooks
R7.1 — Standard hooks
The term “standard hook” as used in this Code shall
mean one of the following:
Recommended methods and standards for preparing design
drawings, typical details, and drawings for the fabrication
and placing of reinforcing steel in reinforced concrete
structures are given in the ACI Detailing Manual, reported
by ACI Committee 315.7.1
7.1.1 — 180-degree bend plus 4db extension, but not
less than 65 mm at free end of bar.
7.1.2 — 90-degree bend plus 12db extension at free
end of bar.
All provisions in the Code relating to bar, wire, or strand
diameter (and area) are based on the nominal dimensions of
the reinforcement as given in the appropriate ASTM specification. Nominal dimensions are equivalent to those of a
circular area having the same weight per meter as the
ASTM designated bar, wire, or strand sizes. Cross-sectional
area of reinforcement is based on nominal dimensions.
7.1.3 — For stirrup and tie hooks
R7.1.3 — Standard stirrup and tie hooks are limited to
No. 25 bars and smaller, and the 90-degree hook with 6db
extension is further limited to No. 16 bars and smaller, in
both cases as the result of research showing that larger bar
sizes with 90-degree hooks and 6db extensions tend to pop
out under high load.
(a) No. 16 bar and smaller, 90-degree bend plus 6db
extension at free end of bar; or
(b) No. 19, No. 22, and No. 25 bar, 90-degree bend
plus 12db extension at free end of bar; or
(c) No. 25 bar and smaller, 135-degree bend plus
6db extension at free end of bar.
7.1.4 — Seismic hooks as defined in 2.2.
7.2 — Minimum bend diameters
R7.2 — Minimum bend diameters
7.2.1 — Diameter of bend measured on the inside of
the bar, other than for stirrups and ties in sizes No. 10
through No. 16, shall not be less than the values in
Table 7.2.
Standard bends in reinforcing bars are described in terms
of the inside diameter of bend because this is easier to
measure than the radius of bend. The primary factors
affecting the minimum bend diameter are feasibility of
bending without breakage and avoidance of crushing the
concrete inside the bend.
7.2.2 — Inside diameter of bend for stirrups and ties
shall not be less than 4db for No. 16 bar and smaller.
For bars larger than No. 16, diameter of bend shall be
in accordance with Table 7.2.
R7.2.2 — The minimum 4db bend for the bar sizes
commonly used for stirrups and ties is based on accepted
industry practice in the United States. Use of a stirrup bar
size not greater than No. 16 for either the 90-degree or
135-degree standard stirrup hook will permit multiple
bending on standard stirrup bending equipment.
7.2.3 — Inside diameter of bend in welded wire
reinforcement for stirrups and ties shall not be less
than 4db for deformed wire larger than MD40 and 2db
for all other wires. Bends with inside diameter of less
than 8db shall not be less than 4db from nearest
welded intersection.
R7.2.3 — Welded wire reinforcement can be used for stirrups
and ties. The wire at welded intersections does not have the
same uniform ductility and bendability as in areas that were
not heated. These effects of the welding temperature are
usually dissipated in a distance of approximately four wire
diameters. Minimum bend diameters permitted are in most
cases the same as those required in the ASTM bend tests for
wire material (ASTM A1064M).
American Concrete Institute Copyrighted Material—www.concrete.org
7
90
STRUCTURAL CONCRETE BUILDING CODE (ACI 318M-11) AND COMMENTARY
CODE
COMMENTARY
TABLE 7.2 — MINIMUM DIAMETERS OF BEND
Bar size
Minimum diameter
No. 10 through No. 25
6db
No. 29, No. 32, and No. 36
8db
No. 43 and No. 57
10db
7.3 — Bending
R7.3 — Bending
7.3.1 — All reinforcement shall be bent cold, unless
otherwise permitted by the licensed design professional.
R7.3.1 — For unusual bends with inside diameters less than
ASTM bend test requirements, special fabrication may be
required.
7.3.2 — Reinforcement partially embedded in
concrete shall not be field bent, except as shown in the
contract documents or permitted by the licensed
design professional.
R7.3.2 — Construction conditions may make it necessary to
bend bars that have been embedded in concrete. Such field
bending should not be done without authorization of the
licensed design professional. Contract documents should
specify whether the bars will be permitted to be bent cold or
if heating should be used. Bends should be gradual and
should be straightened as required.
7
Tests7.2,7.3 have shown that A615M Grade 280 and Grade 420
reinforcing bars can be cold bent and straightened up to
90 degrees at or near the minimum diameter specified in
7.2. If cracking or breakage is encountered, heating to a
maximum temperature of 820°C may avoid this condition
for the remainder of the bars. Bars that fracture during bending
or straightening can be spliced outside the bend region.
Heating should be performed in a manner that will avoid
damage to the concrete. If the bend area is within approximately 150 mm of the concrete, some protective insulation
may need to be applied. Heating of the bar should be
controlled by temperature-indicating crayons or other suitable
means. The heated bars should not be artificially cooled (with
water or forced air) until after cooling to at least 320°C.
7.4 — Surface conditions of reinforcement
R7.4 — Surface conditions of reinforcement
7.4.1—At the time concrete is placed, reinforcement
shall be free from mud, oil, or other nonmetallic coatings
that decrease bond. Epoxy-coating of reinforcement in
accordance with standards referenced in 3.5.3.8 and
3.5.3.9 shall be permitted.
Specific limits on rust are based on tests,7.4 plus a review
of earlier tests and recommendations. Reference 7.4
provides guidance with regard to the effects of rust and
mill scale on bond characteristics of deformed reinforcing
bars. Research has shown that a normal amount of rust
increases bond. Normal rough handling generally removes
rust that is loose enough to injure the bond between the
concrete and reinforcement.
7.4.2 — Except for prestressing steel, steel reinforcement with rust, mill scale, or a combination of both
shall be considered satisfactory, provided the minimum
dimensions (including height of deformations) and
weight of a hand-wire-brushed test specimen comply
with applicable ASTM specifications referenced in 3.5.
American Concrete Institute Copyrighted Material—www.concrete.org