Bạn đang xem bản rút gọn của tài liệu. Xem và tải ngay bản đầy đủ của tài liệu tại đây (6.01 MB, 483 trang )
Characteristics and Performance of Transmission Lines 125
This is a simple series circuit. The relationship
between sending-end, receiving-end voltages and
currents can be written as:
1
LMV OP = LM0 Z OP LMV OP
I Q N
1Q N I Q
N
S
R
S
R
...(6.4)
The phasor diagram for the short-line is shown in
Fig. 6.2 for lagging load current.
From Fig. 6.2, we can write
Fig. 6.1: Short line model.
|VS| cos (dS dR) = |I|R cos dR + |I|
X sin dR + |VR|
(dS dR) is very small,
\
...(6.5)
\ cos (dS dR) » 1.0
|VS| = |VR| + |I| (R cos dR
+ X sin dR)
...(6.6)
Equation (6.6) is quite accurate for the normal range
of load.
Fig. 6.2: Phasor diagram.
6.3 VOLTAGE REGULATION
Voltage regulation of the transmission line may be defined as the percentage change in voltage
at the receiving end of the line (expressed as percentage of full-load voltage) in going from noload to full-load.
Percent voltage regulation =
where
NL
FL
|VR |-|VR |
FL
|VR |
´ 100
...(6.7)
NL
|VR | = magnitude of no-load receiving end voltage
FL
|VR | = magnitude of full-load receiving end voltage
NL
At no load, IR = 0, VR = VR and from eqn. (6.3),
NL
VR =
VS
A
...(6.8)
Using eqns. (6.7) and (6.8), we get,
Percentage Voltage regulation =
|VS| -|A |VR |
| FL
|A |VR |
| FL
´ 100
...(6.9)
FL
For a short line, |A| = 1.0, |VR | = |VR|
\ Percent voltage regulation =
|VS|-|VR|
´ 100
|VR|
Using eqns. (6.10) and (6.6), we get,
...(6.10)
126
Electrical Power Systems
Percent voltage regulation =
|I |( R cos d R + X sin d R )
´ 100
|V R|
...(6.11)
In the above derivation, dR has been considered positive for a lagging load. dR will be
negative, for leading load. Therefore, for leading power factor load,
Percent voltage regulation =
|I|( R cos d R - X sin d R )
|VR|
...(6.12)
From the above equations, it is clear that the voltage regulation is a measure of line voltage
drop and depends on the load power factor.
6.4 MEDIUM TRANSMISSION LINE
For the lines more than 80 km long and below 250 km in length are treated as medium length
lines, and the line charging current becomes appreciable and the shunt capacitance must be
considered. For medium length lines, half of the shunt capacitance may be considered to be
lumped at each end of the line. This is referred to as the nominal p model as shown in Fig. 6.3.
The sending end voltage and current for the nominal p model are obtained as follows:
Fig. 6.3: Medium length line, nominal p representation.
From KCL, the current in the series impedance designated by IL is
Y
VR
2
From KVL, the sending end voltage is
IL = IR +
...(6.13)
VS = VR + ZIL
...(6.14)
From eqns. (6.14) and (6.13), we get,
FG
H
VS = 1 +
IJ
K
ZY
V R + ZIR
2
...(6.15)
The sending end current is,
Y
VS
2
From eqns. (6.16), (6.15) and (6.13), we get,
IS = IL +
FG
H
IS = Y 1 +
IJ FG
K H
...(6.16)
IJ
K
ZY
ZY
VR + 1 +
IR
4
2
...(6.17)
Characteristics and Performance of Transmission Lines 127
Eqns (6.15) and (6.17) can be written in matrix form.
LMFG1 + ZY IJ Z OP LV O
LMV OP = MMH 2ZYK ZY PP MM PP
N I Q MY FGH1 + IJK FGH1 + IJK P MNM I PQP
2 P
MN 4
Q
R
S
S
...(6.18)
R
Therefore, the ABCD constants for the nominal p model are given by
FG
H
A= 1+
FG
H
IJ
K
ZY
, B = Z,
2
C=Y 1+
IJ
K
FG
H
ZY
ZY
, D= 1+
2
4
IJ
K
6.5 LONG TRANSMISSION LINE
For short and medium length lines, accurate models were obtained by assuming the line
parameters to be lumped. In case the lines are more than 250 km long, for accurate solutions
the parameters must be taken as distributed uniformly along the length as a result of which the
voltages and currents will vary from point to point on the line. In this section, expressions for
voltage and current at any point on the line are derived. Then, based on these equations, an
equivalent p model is obtained for long transmission line. Figure 6.4 shows one phase of a
distributed line of length l km.
Fig. 6.4: Schematic diagram of a long transmission line with
distributed parameters.
From KVL, we can write,
V(x + Dx) = z.Dx.I(x) + V(x)
\
As
V ( x + Dx) - V ( x)
= z.I(x)
Dx
...(6.19)
Dx ® 0
dV ( x)
= z.I(x)
dx
...(6.20)
128
Electrical Power Systems
From KCL, we can write,
I(x + Dx) = I(x) + y. Dx .V(x + Dx)
\
As
I ( x + Dx) - I ( x)
= y.V(x + Dx)
Dx
...(6.21)
Dx ® 0
dI ( x)
= y.V(x)
dx
...(6.22)
Differentiating eqn. (6.20) and substituting from eqn. (6.22), we get,
d 2 V ( x)
dx
\
2
d 2 V ( x)
dx 2
dI ( x)
= z. yV(x)
dx
zy V(x) = 0
g2 = zy
Let
Therefore,
= z×
d 2 V ( x)
dx 2
...(6.23)
...(6.24)
g2V(x) = 0
...(6.25)
The solution of the above equation is
V(x) = C1 eg x + C2 eg x
...(6.26)
where, g, known as the propagation constant and is given by,
g = a + jb =
zy
...(6.27)
The real part a is known as the attenuation constant, and the imaginary part b is known as
the phase constant. b is measured in radian per unit length.
From eqn. (6.20), the current is,
I(x) =
1 dV ( x)
×
Z
dx
\
I(x) =
g
(C1 egx C2 egx)
z
\
I(x) =
\
I(x) =
y
(C1 egx C2 egx)
z
1
(C egx C2 egx)
ZC 1
...(6.28)
where, ZC is known as the characteristic impedance, given by
ZC =
z
y
...(6.29)
Characteristics and Performance of Transmission Lines 129
Now note that, when x = 0, V(x) = VR and from eqn. (6.26), we get
VR = C1 + C2
...(6.30)
also when x = 0, I(x) = IR and from eqn. (6.28), we get,
IR =
1
(C1 C2)
ZC
...(6.31)
Solving eqns. (6.31) and (6.32), we obtain,
C1 =
VR + ZC IR
2
...(6.32)
C2 =
(VR - ZC IR )
2
...(6.33)
Substituting the values of C1 and C2 from eqns. (6.32) and (6.33) into eqns. (6.26) and (6.28),
we get
V(x) =
(VR + Z C I R ) gx (V R - Z C I R ) - gx
e +
e
2
2
...(6.34)
I(x) =
(VR + Z C I R ) g x (V R - ZC I R ) - g x
e e
2 ZC
2 ZC
...(6.35)
The equations for voltage and currents can be rearranged as follows:
( e gx + e - gx )
(e gx - e - gx )
VR + Z C
IR
V(x) =
2
2
I(x) =
or
( e gx - e - gx )
(e gx + e - g x )
VR +
IR
2 ZC
2
...(6.36)
...(6.37)
V(x) = cosh(gx)VR + ZC sinh(gx) IR
...(6.38)
1
sinh(gx)VR + cosh(gx)IR
ZC
...(6.39)
I(x) =
Our interest is in the relation between the sending end and the receiving end of the line.
Therefore, when x = l, V(l) = VS and I(l) = IS. The result is
VS = cosh (g l)VR + ZC sinh(g l )IR
IS =
Therefore, ABCD constants are:
1
sinh (gl ) VR + cosh(g l )IR
ZC
A = cosh(g l ) ; B = ZC sinh(g l)
...(6.40)
...(6.41)
...(6.42)
1
sinh(g l ) ; D = cosh(g l )
...(6.43)
ZC
It is now possible to find an accurate equivalent p model for long transmission line as shown
in Fig. 6.5.
C=
130
Electrical Power Systems
Similar to the expressions of eqns. (6.15) and (6.17) obtained for the nominal p, for equivalent
p model we have,
FG
H
VS = 1 +
FG
H
IJ
K
Z¢Y ¢
VR + Z ¢ I R
2
IS = Y ¢ 1 +
IJ
K
FG
H
...(6.44)
IJ
K
Z¢Y ¢
Z ¢Y ¢
VR + 1 +
IR
4
2
...(6.45)
Now comparing eqns. (6.44) and (6.45) with eqns. (6.40) and (6.41), respectively and making
use of the identity
tanh
FG gl IJ = cosh(g l) - 1
H 2 K sinh (gl)
...(6.46)
the parameters of equivalent p model are obtained as:
Z¢ = ZC sinh(g l) =
FG IJ
H K
Z × sinh(g l)
gl
1
Y tanh (g l 2)
gl
Y¢
tanh
=
=
ZC
2
2
gl 2
2
...(6.47)
...(6.48)
Fig. 6.5: Equivalent p model for long transmission line.
Example 6.1: A single phase 60 Hz generator supplies an inductive load of 4500 kW at a power
factor of 0.80 lagging by means of an 20 km long overhead transmission line. The line resistance
and inductance are 0.0195 W and 0.60 mH per km. The voltage at the receiving end is required
to be kept constant at 10.2 kV.
Find (a) the sending end voltage and voltage regulation of the line; (b) the value of the
capacitors to be placed in parallel with the load such that the regulation is reduced to 60% of that
obtained in part (a); and (c) compare the transmission efficiencies in parts (a) and (b).
Solution: The line constants are:
R = 0.0195 × 20 = 0.39 W
X = 0.60 × 103 × 2p × 60 × 20 = 4.52 W
(a) This is a short line with I = IR = IS given by
|I| =
4500
Amp = 551.47 Amp.
10.2 ´ 0.80
Characteristics and Performance of Transmission Lines 131
From eqn. (6.6),
|VS| » |VR| + |I|(R cos dR + X sin dR)
Here
|VR| = 10.2 kV = 10200 Volt
cosdR = 0.8, sindR = 0.6
\
|VS| = 10200 + 551.47 (0.39 × 0.8 + 4.52 × 0.6)
\
|VS| = 11.867 kV
\
Voltage regulation =
(11.867 - 10.2)
´ 100 = 16.34%
10.2
(b) Voltage regulation desired = 0.60 × 16.34 = 9.804%
Therefore, under this condition we can write
|VS| - 10.2
= 0.09804
10.2
\
|VS| = 11.2 kV
Figure 6.6 shows the equivalent circuit of the
line with a capacitor in parallel with the load.
Assuming combined power factor of the load and
capacitor = cos dR¢
Fig. 6.6
By using eqn. (6.6), we can write,
(11.2 10.2) × 103 = |IR| (R cos dR¢ + X sin dR¢)
...(i)
Since the capacitance does not draw any real power, we have,
|IR| =
4500
10.2 cosd ¢R
From eqns. (i) and (ii), we get
4.52 tan dR¢ = 1.876
\
tan dR¢ = 0.415
\
dR¢ = 22.5°
\
\
Now
cos dR¢ = 0.9238
|IR| = 477.56 Amp.
IC = IR I,
IR = 477.56 -22.5° = 441.2 j182.75
I = 551.47 -36.87° = 441.2 j330.88
\
IC = 441.2 j182.75 441.2 + j330.88
\
IC = j148.13 Amp.
Now
XC =
V
1
10.2 ´ 1000
= R =
2p ´ 60 ´ C
148.13
IC
...(ii)
132
Electrical Power Systems
\
C = 38.5 mF Ans.
(c) Efficiency of transmission
Output
4500
=
Output + losses 4500 + (55147 )2 ´ 0.39 ´ 10 -3
.
= 97.43%
Case (a)
h=
Case (b)
h=
4500
= 98.06%
4500 + (477.56) 2 ´ 0.39 ´ 10 -3
It is to be noted that by placing a capacitor in parallel with the load, the receiving end power
factor improves from 0.80 to 0.9238.
Example 6.2: A 220 kV, three phase transmission line is 60 km long. The resistance is 0.15 W/
Km and the inductance 1.4 mH/Km. Use the short line model to find the voltage and power at
the sending end and the voltage regulation and efficiency when the line is supplying a three
phase load of
(a) 300 MVA at 0.8 pf lagging at 220 kV
(b) 300 MVA at 0.8 pf leading at 220 kV
Solution:
R = 0.15 × 60 = 9 W
Assuming
\
f = 50 Hz.
X = 2p × 50 × 1.4 × 103 × 60 = 26.39 W.
(a) Receiving end voltage per phase is
VR =
220 0°
3
= 127 0° kV
The three phase apparent power is 300 MVA at 0.8 pf lagging
\
f = 36.87°
\
S = 300 36.87° = (240 + j180) MVA
The current per phase is given by
IR =
\
S*
*
3 VR
=
300 -36.87°
3 ´ 127 0°
´ 10 3 Amp
IR = 787.4 -36.87° Amp
From eqn. (6.6), the sending end voltage magnitude is
|VS| = |VR| + |I| (R cos dR + X sin dR)
|VR| = 127 kV, |I| = 787.4 Amp = 0.7874 kA,
R = 9 W, X = 26.39 W
cosdR = 0.8, sindR = 0.6
\
|VS| = 127 + 0.7874 (9 × 0.8 + 26.39 × 0.6)
Characteristics and Performance of Transmission Lines 133
\
|VS| = 145.13 kV.
\ Sending end line-to-line voltage
|VS|LL =
Voltage regulation =
3 × 145.13 = 251.37 kV
25137 - 220
.
= 14.26%
220
Per phase real power loss in the line
PLoss = |I|2 R = (787.4)2 × 9 × 106 MW = 5.58 MW.
Per phase receiving end power
PR =
300
´ 0.8 = 80 MW
3
\ Per phase sending end power
PS = (80 + 5.58) = 85.58 MW.
Transmission line efficiency is
h=
(b)
PR
80
=
= 93.47%.
PS 85.58
3 |VR||IR| = 300
\
\
as:
|VR| = 220 kV
|IR| = 787.4 Amp
Load is at 0.8 power factor leading. For leading power factor load, eqn. (6.6) can be written
|VS| = |VR|+ |I| (R cos dR X sin dR)
\
\
|VS| = 127 + 787.4 (9 × 0.8 26.39 × 0.6) = 120.2 kV
|VS|LL =
Voltage regulation =
3 × 120.2 = 208.2 kV
208.2 - 220
= 5.36%
220
Per phase real power loss = (787.4)2 × 9 × 106 = 5.58 MW
Per phase receiving end power,
PR =
300
´ 0.8 = 80 MW
3
Per phase sending end power,
PS = (80 + 5.58) = 85.58 MW
Transmission line efficiency
h=
PR
80
=
= 93.47%
PS 85.58
134
Electrical Power Systems
Example 6.3: Determine the efficiency and regulation of a 3-phase, 150 km long, 50 Hz
transmission line delivering 20 MW at a power factor of 0.8 lagging and 66 kV to a balanced
load. Resistance of the line is 0.075 W/km, 1.5 cm outside dia, spaced equilaterally 2 meters
between centres. Use nominal p method.
Solution:
R = 0.075 × 150 = 11.25 W
diameter of the conductor = 1.5 cm
1.5
= 0.75 cm
\
radius r =
2
d = 2 mt = 200 cm
FGH 200 IJK Henry
0.75
\
L = 2 × 107 × (150 × 1000) ln
\
\
L = 0.1675 Henry
X = 2 × p × 50 × 0.1675 = 52.62 W.
The capacitance per phase =
\
\
\
2 ´ p ´ 8.854 ´ 10 -12
´ (150 ´ 1000) = 1.49 mF.
200
ln
0.75
FGH IJK
Y = jwC = j 2p × 50 × 1.49 × 106 mho
Y = j 468.1 × 106 mho
Y
= j 234 × 106 mho
2
Z = (11.25 + j52.62) = 53.809 77.9° W.
Now
3 × |IR|× 66 × 0.8 = 20 × 1000
\
|IR| = 218.7 Amp. at 0.8 pf lagging
Receiving end phase voltage
|VR| =
From eqn. (6.15), we have
66
3
FGH
= 38.104 kV
IJK
VS = 1 + ZY VR + Z IR
2
IR = 218.7 -36.87°
VR = 38.104 0°
ZY
= 53.809 × 234 × 106 77.9° + 90°
2
= 0.01259 167.9° = (0.0123 + j0.00264)
Characteristics and Performance of Transmission Lines 135
VS = (1 0.0123 + j0.00264) × 38.104 0° +
\
(53.809 77.9° ´ 218.7 -36.87°)
1000
\
.
VS = (0.9877 + j0.00264) × 38.104 0° + 11.76 4103°
\
VS = 37.63 + j0.1 + 8.87 + j7.72
\
VS = (46.5 + j7.82) = 47.15 9.54° kV
\
3 × 47.15 9.54° kV = 8166 9.54° kV
.
VS(L L) =
FGH
IJK
81.66
|VS|
- 66
-|VR|
0.9877
|
Voltage regulation VR = |A
= 25.26%
=
66
|VR|
Power loss per phase = |I|2 R = (218.7)2 × 11.25 × 106 MW = 0.538 MW
Per phase receiving end power
PR =
20
MW
3
Per phase sending end power
PS =
20
+ 0.538 = 7.204 MW
3
Transmission efficiency
h=
20 3
= 92.54%.
7.204
Example 6.4: Determine the voltage, current and power factor at the sending end of a 3 phase,
50 Hz, overhead transmission line 160 km long delivering a load of 100 MVA at 0.8 pf lagging
and 132 kV to a balanced load. Resistance per km is 0.16 W, inductance per km is 1.2 mH and
capacitance per km per conductor is 0.0082 mF. Use nominal p method.
Solution:
R = 0.16 × 160 = 25.6 W
X = 1.2 × 103 × 2p × 50 × 160 = 60.3 W.
Y = j2p × 50 × 0.0082 × 106 × 160 = j4.12 × 104 mho
Z = R + jX = 25.6 + j60.3 = 65.51 67° W.
From eqn. (6.15),
FGH
VS = 1 +
IJK
ZY
VR + ZIR
2
Phase voltage at the receiving end,
VR =
132
3
0° kV = 76.21 0° kV