Bạn đang xem bản rút gọn của tài liệu. Xem và tải ngay bản đầy đủ của tài liệu tại đây (33.91 MB, 678 trang )
288
Electrical installations in hazardous areas
over-pressure relief device in the enclosure so that if there is any unwanted
pressure elevation in service the enclosure is automatically safeguarded.
A requirement for the enclosure to be weather proof is not necessary
as the pressurization requirements will effectively prevent the ingress of
moisture. Prevention of entry of solid foreign bodies, however, remains
necessary as these may still enter due to their nature and, unlike moisture,
will not be easily removed by purging if they enter prior to energization.
A requirement is for the enclosure to have an integrity of not less than
IP40 in accordance with BS/EN 605298 in the absence of the pressurizing
gas. In the case of rotating machines where IP-ratings are defined slightly
differently, due to the nature of such apparatus, the Standard used is EN
60034-5, which is published in the UK as BS 4999, Part 105.9
When considering the IP-rating of the enclosure, the deliberate apertures
for inlet and outlet of the purge gas may be ignored. These, however, must
be sited to ensure adequate purging and the avoidance of dead spots where
any flammable gas or vapour may dwell even after purging. This may only
require careful siting of single apertures in each case but may, where enclosure shapes are complex or components create divisions in the enclosure,
need several inlet and outlet apertures. The choice is one which can only
be made individually but it is not likely that multiple apertures will be
the norm.
Where outlet apertures are fitted to enclosures which are pressurized
by static pressurization or pressurization with leakage compensation, these
must be arranged so that they can be closed or sealed after purging by
devices which form part of the apparatus.
It is recognized that the apparatus will, in common with other types
of apparatus, be fitted with doors and covers which permit access to the
interior of the enclosure. The ideal method of dealing with these in the
case of pressurization with leakage compensation, and pressurization with
continuous dilution, is to utilize an interlock which isolates the electrical
supplies and any other electrical connections (see Fig. 11.2) when the door
or cover is opened. Because this would limit the opportunity for adjustment
it is possible to introduce an interlock defeat system (see Fig. 11.3) which
would permit competent persons to open the enclosures, under a system
of control, for adjustment and similar purposes without electrical isolation.
After such work, when the enclosure is reclosed it is important that the
system goes through its full purge cycle to remove any gas which has
entered, although it is not necessary to isolate the electrical supplies during
this period.
Where a tool or key is required to open doors or remove covers isolation is not necessary, but the purge cycle needs initiating after reclosure.
In this case it will have to be done manually. A device can be fitted which
recognizes opening or removal, and isolates electrical supplies with an override as already described. The tool or key requirement in this case does not
indicate any requirement for 'special fasteners' or the like (see Chapter 8).
In the case of static pressurization, doors and covers will not be provided
for adjustment after pressurization due to the nature of the approach. All
Protection concept pressurization ‘p’ 289
I
I
-1
I
1
Pressurized
enclosure
Other
electrical
circuits
I
I
I
I
I
I
I
I
I
Fig. 11.2 Disconnection of electrical supplies and circuits on pressure failure
Purged
enclosure
Pressure switch
NOT PREFERRED
PREFERRED
Fig. 11.3 Defeating of control system. Note. The preferred method ensures the
repurge of the enclosure after reinstatement of pressure.
290 Electrical installations in hazardous areas
that is required is for any doors or covers to need a tool or key for them to
be opened or removed. Once again, the requirement for a tool or key does
not indicate a requirement for the 'special fasteners' described in Chapter 8.
11.5.2Ducting
As the ducting forms part of the enclosure it needs to satisfy the same
requirements as those for enclosures. With the use of compressed gas, this
is no problem as the ducts will be short, being only in the area of the
enclosure (see Fig. 11.4) - the supply of gas to that point normally being
compressed gas piping, and the outlet ducting being short as it discharges
into the hazardous area. (It is not possible to permit the exit ducting to
exhaust into a non-hazardous area, as to do so would make it a hazardous
area). Therefore, in these cases, all piping and ducting will be at a pressure
above atmospheric pressure and the ducts can form a part of the apparatus.
Where the protective gas is air, and fan supplied (not normally possible
for inert gas), then there are two possibilities. First, the fan and immediate
ducting may form part of the enclosure and be under the control of the
manufacturer. The air must, however, be obtained from a non-hazardous
area resulting in a considerable length of ducting. This, then, becomes an
installer problem. Which makes matters very difficult because the pressure
Pressure
Pressurized
enclosure
Atmospheric pressure
Fig. 11.4 Pressurization using compressed gas
Protection concept pressurization ‘p’ 291
in the supplying duct will be below atmospheric pressure (see Fig. 11.5)
and, as the ducts must pass through a hazardous area, any leak will permit
the possible entry of an explosive atmosphere into the enclosure. This first
approach is not, therefore, recommended and the alternative of the remote
fan with pressurized ducting is preferred (see Fig. 11.6).
Where the exhaust ducting is short and discharges into a hazardous
area any incandescent sparking inside the enclosure can, in certain
circumstances, cause the ejection of incandescent particles into the
hazardous area. A device to prevent such ejection is normally necessary
when the apparatus produces ignition-capable sparking which can give
rise to such particles or contains some other mechanism (for example, a
flame ionization chromatograph), which can in normal operation, and the
exhaust duct discharges into any hazardous area and when even though
the apparatus does not itself produce such particles in normal operation
but the exhaust ducting exhausts into a Zone 1. This latter is to cover the
Hazardous area
Pressure
switch
Non-hazardous
area
Fan delivery
pressure
I
50 N/mz minimum
I
I
Atmospheric pressure
Fan inlet
pressure
Fig. 11.5 Fan pressurizing with fan at enclosure inlet
Non-hazardous
area
1
Pressure
switch
Hazardous area
Pressurized
enclosure
I
Ducting
pressure
-
50 Nlm2 minimum
i
Atmospheric pressure
Fan inlet
pressure
Fig. 11.6 Fan pressurizing with fan in non-hazardous area
292
Electrical installations in hazardous areas
situation where internal electrical fault can cause the incandescent particles.
Table 11.2 produces this in tabular form.
Table 11.2 Requirements for spark and particle barriers
Necessity for spark/particle barrier
Apparatus sparks in
Apparatus does not
normal operation
spark in normal
operation
Zone into
w i h purge
hc
gas exhausts
Exhaust not permitted
Barrier required
Barrier required
Barrier not required
Zone 0
Zone 1
Zone 2
Non-hazardous
Exhaust not permitted
Barrier required
Barrier not required
Barrier not required
worn BSEN 50026)
Spark-arresting devices are usually labyrinthine devices or, for example,
steel wool (see Fig. 11.7).
Finally, it must be noted that the exhaust ducts provide a route for
explosive atmosphere entry in periods when no pressurization is present.
Therefore, some method of preventing or slowing down entry of such atmospheres is necessary as part of the procedure for restricting the rate of entry
of explosive atmosphere on pressurization failure or electrical isolation.
Lengthwise
cross-section
End cross-section
Labyrinth
Exhaust gas b
-abyrinthine
Retaining
gauze
Filled
Fig. 11.7 Spark and particle arresters
1 1.5.3 Internal electrical components, etc
As the internal parts of the enclosure are protected by pressurization, the
requirements for them are normally only those which would be required
for normal industrial use. There are some special conditions however.
Protection concept pressurization ‘p’ 293
Leak of
flammable
matenal
Plume area where
possible flammable
atmosphere is present
during dilution
\
Flammable
material
b
components
No ignition
capable
electrical
components
/
Dilution
outlet
FIammabIe
v
-* material
Pressurized enclosure
Fig. 11.8 Internal release of explosive atmosphere
Where the pressurized enclosure contains other enclosures such as those
normally fitted to the enclosed equipment (e.g., relay cases, television
monitor cases, etc.) it is possible that these could fill with an explosive
atmosphere and not be effectively purged. For this reason the inner
enclosures should either be removed or have large holes cut in to ensure
that the purge is effective. The easier way is normally to remove the internal
enclosure. This is not necessary when the inner enclosure is effectively
sealed by some means. Elastomeric seals in addition to fusion seals are
considered adequate for this purpose.
There is a further possible problem in that where an internal release
of flammable material occurs an explosive atmosphere may occur in the
region of the release before complete dilution of the release has taken
place by the continuous flow of protective gas (if that gas is air or if
oxygen is contained in the release itself). In these circumstances all electrical
components, other than those which are rendered non-ignition capable by
another protection concept, should be kept well away from the dilution
area (see Fig. 11.8). This is normally achieved by ensuring that no unprotected electrical components are near the line of sight from the release to the
enclosure exit aperture. This can be assured by siting the possible source of
leakage between the electrical components and the exit aperture. This does
not apply, of course, to deliberate ignition sources such as flames in flame
ionization chromatographs and their ignitors.
11.6 Safety provisions and devices
It is clear that the security of this protection concept relies to a very large
extent upon the monitoring and control devices which ensure that purging
is effective and pressurization is maintained. As in all cases, except those
associated with pressure maintenance in static pressurization, these are
not always provided by the manufacturer. It appears at first sight to be
somewhat incongruous that a formal Standard is written for a protection
294
Electrical installations in hazardous areas
concept which is less controlled by the manufacturer than others. This is
not, however, true as a close look at any installation using any protection
concept will show that much of its safety is determined by installation
matters (e.g., what electrical protection provisions are made,? what cables
are used?, etc.). Therefore, the situation where the purge and pressurization
sensing devices and their associated control devices are only controlled by
specification is acceptable.
Pressure and purge rate detection devices should, as far as possible, be
sited at or near the enclosure outlet to avoid incorrect identification of the
purge/pressure situation occurring (e.g., a gas leak at the input of the purge
gas causing identification of correct purge when, in fact, gas is leaking before
it enters the enclosure, or identifymg correct over pressure when inlet to
enclosure is blocked). In addition, small bore connections to such devices
should be avoided as far as possible to prevent blockage.
The sequences for purging should be as follows for all three applications
of the technique:
1. Detectors should identify that minimum pressure and flowrate is
achieved before timing of purge is commenced.
2. If pressure or purge flowrate falls below the specified minimum specification during the purge, the purge should cease and the control circuits
should recommence purge when the minimum conditions have been
restored.
3. After purging, in the case of pressurization with leakage compensation
or with continuous dilution, the control system should close purging exit
valves and continue to monitor pressure and, in the case of continuous
dilution, gas flow.
4 On failure of either pressure, or in the case of continuous flow, gasflow
.
provision must be made for an alarm to be sounded or complete electrical
isolation the choice being made by the user.
5. If the enclosure is opened, even if alarm or isolation action is overridden
by maintenance control circuits, the apparatus must go through its entire
purge cycle on reclosure as soon as the purge conditions have been
established.
It is possible to pressurize several enclosures from the same source but
care must be taken in so doing. If they are pressurized in series, it is likely
that failure of pressure in any one enclosure will cause failure in all downstream enclosures. In this case the corrective action on any single failure
must apply to all affected enclosures. Even if this is not the case any single
failure will initiate the repurging of all enclosures. Where the common
pressurization source is pressurizing the enclosures in parallel, this situation does not occur and, provided the failure of any one enclosure can be
uniquely identified, it is only necessary to repurge that one enclosure after
correction.
The reliability of the purge and pressurization control devices is
fundamental to the security of the protection concept. A European Standard
Protection concept pressurization ‘p’ 295
(EN 954)1° is in preparation and will concern itself with the reliability
of safety related circuits and devices, but until this is available there is
no European Standard which can be effectively applied. General safety
approaches (e.g., fail to safety) should govern the design of systems and
if there is any doubt in a particular case, duplication of components or
circuits should be considered.
References
1 CP 1003
Electrical Apparatus and Associated Equipment
for use in Explosive Atmospheres of Gas or
Vapour Other Than Mining operations. Part 2 (1966).
Methods of Meeting the Explosion Hazard Other
Than by the Use of Flameproof and Intrinsically Safe
Equipment.
National Electrical Code (USA). Article 500,
hazardous (Classified) Locations.
3 76/117/EEC (1975) Council Directive on the Approximation of the Laws
of Member States Concerning Electrical Equipment
for Use in Potentially Explosive Atmospheres.
December.
Centre Europeen de Normalization Electrique.
4 CENELEC
Electrical Apparatus for Potentially Explosive Atmo5 B 5501
S
spheres. Part 3 (1977). Pressurized Apparatus ‘p’.
2 NEC 70 (1990)
6 BS/EN 50016 (1996) Electrical Apparatus for Potentially Explosive
Atmospheres. Pressurized Apparatus ’p’.
7 BS/EN 50014 (1993) Electrical Apparatus for Potentially Explosive
Atmospheres. General Requirements.
8 BS/EN 60529 (1991) Specification for Degrees of Protection Provided by
Enclosures (IP Code).
General Requirements for Rotating Electrical Mach9 BS 4999
ines. Part 105 (1988). Specification for Degrees of
Protection Provided by Enclosures for rotating
Machinery.
10 EN 954
Safety of Machinery - Safety Related Parts of
Control Systems (in Preparation).
12
Apparatus with protection concept
increased safety ‘e’
(BS/EN 50019 (1994))
The protection concept (type of protection) of increased safety is one
intended for use in Zone 1 and less hazardous areas. It is a German
development (erhohtesichereit) which explains the use of ’e’ as its concept
symbol. Increased safety did not figure significantly in UK thinking before
1970 and only became important then because of the effect on UK
attitudes produced by the increasing importance of the European dimension
emerging at the time of the European Free Trade Association (EFTA), of
which the UK was a member prior to its entry into the European Union
(EU). It gained further importance in UK thinking with the UKs entry into
the EU itself.
It is a type of protection where, even though the ingress of an explosive
atmosphere into the enclosure is not prevented, the apparatus does
not spark, arc or become excessively hot in normal operation and, in
addition, is of such quality that it is unlikely to become faulty in a way
which would make it ignition capable. This security from fault is further
increased by enclosure protection from its environment, reducing the risk of
environmental conditions adversely affecting its operation. The protection,
however, is much more sensitive to electrical protection devices (fuses,
circuit breakers, etc.) than the other types of protection so far considered
as any fault (e.g., internal short circuit, connection failure, etc.) is likely to
make it ignition capable. Therefore part of the protection depends upon the
length of time for which such a situation can exist prior to the protective
devices operating.
There were many misgivings in the UK concerning the adoption of
increased safety as a protection concept suitable for Zone 1 and less
hazardous areas, particularly for such things a rotating machines and
luminaires, as the requirements for the protection concept in the German
National Standard (VDE 0171) did not, to many, appear to offer a significant
increase in the requirements applied by British Standards to Standard
industrial equipment of these types in UK. There is still considerable
concern in respect of rotating electrical machines and this is dealt with
later in this chapter.
Despite this reservation it was accepted that increased safety would
become a standard protection concept in Europe and the world at large
and to exclude it in the UK for what were, to the majority in the UK,
Protection concept increased safety 'e' 297
unconvincing techrucal reasons (no real evidence existing at the time of its
level of protection being too low, rather than historic UK approaches being
too high) would merely damage UK manufacturing industry. It was also
noted that an International Standard (IEC 79-7 (1969)') was likely to be
accepted by most countries of the world.
12.1 The situation in regard to standardization
The UK accepted the protection concept of increased safety and a National
Standard was produced in 1973 (BS 4683, Part 4*). This Standard was
rapidly overtaken by BS 5501 Part 6 (1977)3 (which was the first edition
of a European Standard, EN 50019) and both of these Standards have now
been overtaken by BS/EN 50019 (1994)4 which is the second edition of
the European Standard and will, in effect, be the Standard to which future
apparatus will be constructed. This chapter will therefore be based upon
the requirements of BS/EN 50019.
12.2 Basic construction requirements
The basic security of increased safety apparatus is in the construction of the
apparatus itself and the limitations of the types of apparatus to which the
protection concept is applicable. These limitations are:
1. The apparatus must not arc or spark or produce ignition capable hot
surfaces in normal operation
2. No apparatus operating at a supply voltage of more than 11kV rms, or
which internally produces voltages in excess of this, can be protected
within this protection concept.
3. Apparatus where component construction cannot be defined in a way
which will permit compliance with the requirements of the protection
concept, or which cannot comply by virtue of their construction (e.g.,
semiconductor devices) cannot be dealt with in this protection concept.
Therefore, increased safety is not normally applicable to instrumentation.
The above means that the protection concept finds its greatest
application in such apparatus as connection boxes, luminaires, rotating
machines, transformers, batteries, resistance heating devices and measuring
instruments (basic meters, etc.).
12.2.1 Construction of enclosures
Enclosures need to comply with the general hazardous area requirements
(see Chapter 8) but because of the nature of this protection concept they
must satisfy additional requirements.
298 Electrical installations in hazardous areas
As previously stated, the protection concept relies to a high degree on
the exclusion of the external environment (keeping out the weather but not
gas) and to this end the enclosures must have a degree of protection of at
least IP54 in accordance with BS/EN 605295 (As elsewhere, the method
of determination of IP-rating for rotating electrical machines is slightly
different and BS 4999 part 1056 is used in place of BS/EN 605295 for
such machines). Where the enclosure contains only insulated conductors
and components, rather than bare live parts, this enclosure integrity may
be reduced to IP44. Further reductions are permissible if breathing or
draining holes are necessary for the reliable operation of the apparatus.
In these circumstances IP44 is acceptable for enclosures containing bare
live parts, and IP24 for enclosures containing only insulated conductors
and components. In these latter cases, to utilize the lower IP-ratings, the
position of the holes is critical and the apparatus will be subjected to
installation conditions which minimize the possibility of ingress of liquid
or solid foreign bodies in its installed location.
The requirements become more complex when this protection concept is
used in conjunction with intrinsic safety (see Chapter 13 which discusses
intrinsic safety) as is sometimes the case when it needs internal monitoring
devices (e.g., temperature sensors in rotating machine windings) to ensure
that early isolation takes place in case of fault. It is clear that the actual
construction of the apparatus must be such that the intrinsic safety is not
compromised but there is a particular point where outside influences can
produce such a compromising effect. This is where the external connections
are made for the increased safety part of the apparatus in the same place
(terminal box, etc.) as the intrinsic safety external connections. In these
circumstances an inner cover of at least IP30 is necessary for the increased
safety connection facilities and a warning is necessary to ensure that this
cover is not removed when the outer cover is off and the increased safety
terminations energized or the intrinsically safe circuits are connected to
external circuits. The inadvertent application of the levels of voltage in most
increased safety apparatus could damage an intrinsically safe installation
in a way which would not be apparent and which may cause danger, not
only in the particular installation but in other intrinsically safe installations
using facilities in common with it.
These enclosures and covers need to be fixed by special fasteners as
described in Chapter 8.
12.2.2Terminals and connection facilities
All electrical connections, both those within the apparatus and those to
permit connection of external electrical conductors, are important in this
concept as any failure, even partial, of a connection can give rise to sparking.
Of the possible electrical connections for external conductors themselves,
only terminals are specifically addressed with specific detailed requirements
which have to be satisfied to ensure they are reliable. The general use
of plugs and sockets is not specifically mentioned in any Standards for